Record calibration factors, Figure 4-6: flow sensor calibration factor, Simulated flow – Hale FoamLogix 6.5 User Manual
Page 115: Figure 4-7: simulated flow calibration

Se tup and Cal ibration
❑
115
FoamLogix 3.3 / 5.0 / 6.5 Installer / Operations Manual
p/n: 029-0021-68-0
Verify that the reading on the control unit is within 5% of the actual value.
5. STOP the water flow when adjustments are completed.
Record Calibration Factors
1. Press and release the
i
button. The display shows
F xx.x, which is the water
flow sensor calibration
factor. (See Figure 4-6:
“Flow Sensor Calibration
Factor.”)
2. Record this value for
future reference. This fac-
tor can be programmed
into the existing display if
the display is ever
replaced or to provide a
baseline calibration point.
WATER FLOW SENSOR CALIBRATION
FACTOR: _________________________________________
Simulated Flow
The default Simu-
lated Flow value is
factory set to 150
GPM (568 LPM) and,
if necessary, may be
adjusted while in the
user calibration
mode.
1. Press the
i
button. The
default simulated flow
rate is shown. (See
Figure 4-7: “Simulated
Flow Calibration.”)
Figure 4-6: Flow Sensor Calibration Factor
Figure 4-7: Simulated Flow Calibration