10 leak testing the air locker, 4 installing the air locker, Leak testing the air locker – ARB RD158 User Manual

Page 23

Advertising
background image

4 Installing the Air Locker

21

NOTE : Excessive tightening of the center compression nut is

not necessary to form a good seal around the tube
and may damage the O-ring, the seal housing tube, or
the threads of the compression nut.

NOTE : Make sure the seal housing tube is all of the way into

the center compression nut while you are tightening
it.


Again check that no part of the seal housing tube comes in contact

with the moving differential components. Less than 8mm [5/16”]
should be considered too little clearance. Gently bend the tube
away from moving parts if necessary.

4.10

Leak Testing the Air Locker

To test the Air Locker; when 620kPa [90 PSI] shop air is applied to

the seal housing tube, the Air Locker should engage.

Check all fittings and the seal housing for air leaks.
Rotate the differential carrier by turning the pinion flange whilst

applying air pressure.

NOTE : An accurate way to test for air leaks is to fit a shut-off

valve to an air pressure gauge (ARB part # 0770005).
Once 620 KPA [90 PSI] is reached close the valve,
disconnect the air hose, and watch to see if there is any
drop in pressure. If so, this will indicate an air leak.
(Fig. 14.)

Figure 14.









If a leak is found to be present, spray a soap and water mixture

onto the bulkhead air fitting. Bubbles should appear at any leak
points.

Advertising