Gas pressure checks – L.B. White Guardian with Smart Sense / Direct Connect - Spark Ignition (250K) User Manual

Page 19

Advertising
background image

The following explains a typical procedure to be followed in
checking gas pressures.

Consult the dataplate on the heater or page 4 in this
manual for specific pressures to be used in conjunction
with this procedure.

Gas pressure entering the gas valve is Inlet Pressure. Gas
pressure flowing out of the gas valve is Burner Manifold
pressure.

A. Preparation

1.

Obtain two pressure gauges capable of reading up to 35
in. W.C.

2.

Disconnect the heater from the electrical supply and
close the fuel supply valve to the heater inlet.

3.

Open the burner access panel.

4.

Brush or blow off any dust and dirt on or in the vicinity of
the gas control valve.

B. Gauge Installation

1.

Locate the inlet and outlet pressure taps, see Fig. 18.
Using a screwdriver, open the pressure taps by turning
both screws one full turn counterclockwise.

FIG. 18

2. Securely connect a pressure gauge to each pressure tap.

See Fig. 19.

FIG. 19

3.

Open the fuel supply valves to the heater and reconnect
the heater electrical supply.

4.

Start the heater

C. Reading Pressures

1.

S e t t h e b u i l d i n g c o n t ro l l e r to c a l l fo r m a x i m u m
temperature. With the heater operating, the pressure
gauges should read the pressures specified on the
dataplate.

2.

Do the readings at the inlet and outlet pressure gauges
agree with that specified on the dataplate? If so, then no
further checking or adjustment is required. Proceed to
section D.

3.

If the inlet pressure does not agree with that specified on
the dataplate, then the regulator controlling gas pressure
to the heater requires adjustment.

4.

If the inlet pressures are correct but the burner manifold
pressure does not agree with that specifed on the
dataplate, check the heater’s burner orifice for blockage.
if the orifice is unblocked, the gas control is defective
and should be replaced.

D. Completion

1.

Once the proper inlet and burner manifold pressures
have been confirmed and/or properly set, close the fuel
supply valve to the heater and allow the heater to burn
off any gas remaining in the gas supply line.

2.

Disconnect the heater from its electrical supply.

3.

Remove the gauges and connecting hoses.

4.

Close both pressure tap screws by turning clockwise,
snugging in securely. Check for gas leaks.

WARNING

Do not disassemble the gas control valve.

Do not attempt to replace any components of the gas
control valve.

The gas control valve must be replaced if any physical
damage occurs to the control valve assembly.

Failure to follow this warning will result in fire or
explosions, leading to injury or death to humans, and
property damage.

18

Gas Pressure Checks

INLET PRESSURE TAP

OUTLET PRESSURE TAP

Advertising