L.B. White Guardian with Smart Sense / Direct Connect - Spark Ignition (250K) User Manual

Page 25

Advertising
background image

24

If ignition contr

ol module does no

t reset, then replace the contr

ol. (Int

ernal f

ault.)

If ignition contr

ol module resets, then ha

v

e

q

ualif

ied electrician check po

w

er sour

ce

for po

w

er q

uality pr

oblems. (F

req

uency

, line noise, line spik

es, loose connections, t

o

o

small wire gauge.)

Fiv

e Times

Rapid On/Off

cycling of the

burner.

Ignition contr

ol is identifying a flame sense relat

ed

pr

oblem. Burner flame f

ailure ma

y occur

. Check all

gr

ounds, clean the sensor or check f

or cracks in

sensor insulat

or

.

NO

TES:

(1)

The ignition contr

ol sends and receiv

es v

oltages thr

oughout the entire operation seq

uence. The ignition contr

ol’s t

erminals

should also be check

ed f

or deliv

ering pr

oper v

oltages, in addition t

o

the individual com

ponents as indicat

ed b

y the respectiv

e

flash patt

ern.

(2)

The high-limit switch will open or trip f

or a v

ariety of reasons, such as high gas pressure, lo

w v

oltage, e

xcessiv

e dust and

dir

t

build-up within the heat

er

, dir

ty f

an assembly

, f

an is no

t tight

ened ont

o mo

tor shaf

t, and obstructions in air inlets or discha

rge

outlet of heat

er

.

F

our Times

Poor flame

sense.