Wiring sensor wiring, Powering the dcr-1006a, Automation products group, inc – APG DCR-1006A user manual User Manual
Page 9: Red pin 1 (brown), Black pin 3 (blue), Dst sensor, Mnu sensor

Rev. A1, 2/14
DCR-1006A Ultrasonic Controller
9
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
• Wiring
Sensor Wiring
The DCR-1006A is compatible with DST and MNU series ultrasonic sensors.
MNU Standard Cable Micro-Connector
24V
Red
Pin 1 (Brown)
GND
Black
Pin 3 (Blue)
A
White
Pin 2 (White)
B
Green
Pin 4 (Black)
DST
Standard Cable Micro-Connector
+
Red
Pin 1 (Brown)
-
Black
Pin 3 (Blue)
Powering the DCR-1006A
Power to the DCR-1006A can be supplied from either 85-264 VAC or 12-28 VDC.
NOTE: terminals will source 24 VDC
when powering via AC voltage.
OR
GND
Ground
Neutral
Hot
85-264 VAC
INPUT
AC/N (-)
AC/L (+)
Powering with AC Voltage
24V
GN
D
Vs
OUT
DC Voltage Powered
12-24 VDC
INPUT
DST Sensor
DST
+
_
24V
GN
D
Vs
A (-)
B(+)
A1 (-)
B1(+)
OUT
MNU Sensor