Perform checkout procedures • fill out certificate – Carlin 601GAS Inst Manual User Manual

Page 18

Advertising
background image

Model 601GAS burner — Instruction manual

Carlin part number MN601GAS Rev. 04/24/09

– 18 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Installer/servicer

Please check off and fill in certificate

After completing start-up and testing or service, fill out the certificate

on page 28.

Should overheating or an emergency occur, immediately:

• Shut off main manual gas valve.

• Shut off control switch to burner.

Under some circumstances power should remain on for
circulating blowers or other equipment. Determine proper
response before attempting start-up. If appliance fails ignition
on several attempts, close gas valve and use burner blower
to purge appliance before restart.

5. Perform checkout procedures • fill out certificate

Make final burner adjustments

(continued)

Inspect flame

Look at flame through appliance observation port. The flame should

be a soft blue with well-defined orange and yellow tips for natural

gas, or well-defined yellow tips for propane gas. (If you make air or

gas pressure changes later, inspect the flame again.)

Check the firing rate

Natural gas only — Turn off all other gas appliances connected to

the gas meter. Use a stopwatch to time the number of seconds for

a flow of one cubic foot of gas (two revolutions for a one half cubic

foot per revolution dial, for example). You will also need to know the

gas heat content in Btu per cubic foot. Determine the actual input

from: INPUT = (3600 x Btu per cubic foot) ÷ (number of seconds for

one cubic foot), for firing rate in Btuh. For example, for 1050 Btu per

cubic foot natural gas, with meter timed at 15.1 seconds for one cubic

foot of gas: INPUT example = (3600 x 1050) ÷ (15.1) = 250,500 Btuh.

Firing rate should be within ± 5% of rated input for the appliance.

Adjust the gas pressure regulator if necessary to obtain the correct

firing rate. Valve outlet pressure must not be lower than 3.2 inches

w.c. nor higher than 3.8 inches w.c.

For propane gas, contact your propane supply for procedure to verify

firing rate.

Preparation before checkout

Burner/appliance installed per appliance instruction manual?

Burner components/settings verified against Table 1a, page 9?

Burner/appliance installed per all applicable codes?

Installation site has adequate ventilation openings and vent sys-

tem?

Gas supply line in good condition and sized correctly?

All gas line joints sealed with pipe dope listed for use with liquefied

petroleum gases?

Gas supply pressure to gas valves checked?

Regulator installed if pressure can exceed 14 inches w.c.?

Air purged from gas line?

Gas piping checked for leaks?

Wiring installed per burner manual and appliance instructions?

Burner inspected and primary control flame failure lockout checked?

Start-up sequence performed (page 17)?

Make final burner adjustments

Check for leaks in gas piping

Smell around burner to make sure there is no gas leak in near-burner

piping. Verify integrity of gas line joints between gas valves and burner

gas inlet connection using soap suds mixture.

Check/adjust gas valve outlet pressure

With burner running, check manometer reading for gas valve outlet

pressure. Adjust regulator if necessary so the reading is 3.5 inches

w.c. for either natural gas or propane gas.

Check combustion using instruments

Do not attempt to confirm combustion simply by inspecting

the flame visually. You must use combustion test instruments.
Failure to properly verify/adjust combustion could allow
unsafe operation of the burner, resulting in severe personal
injury, death or substantial property damage.

Insert a test probe into appliance vent outlet to sample flue products.

The results should show CO

2

or O

2

as follows:

Fuel

CO

2

O

2

Minimum Maximum Maximum Minimum

Natural Gas

8.5%

10.0%

6.2%

3.5%

Propane Gas

9.5%

11.2%

6.0%

3.5%

If the combustion results are outside the range above, and the firing

rate of the burner is within 5% of rated input, open or close the air

damper until the CO

2

(or O

2

) are acceptable.

After CO

2

(O

2

) tests are completed satisfactorily, measure

flue products for carbon monoxide (CO) concentration. The
CO must not exceed 50 ppm adjust to “air free”, or other if
specified by local codes.

Check overfire pressure in the appliance. Refer to the appliance manual

for recommended reading and barometric damper instructions for

proper setting of damper, when used.

Advertising