601gas massachusetts code burner at-a-glance – Carlin 601GAS Mass Code Supp. User Manual

Page 2

Advertising
background image

Model 601GAS burner — Instruction manual — Supplement – Massachusetts Code

Carlin part number MN601GASM Rev. 05/01/07

–  –

Where appliance instructions differ from this manual, follow the appliance instructions.

601GAS Massachusetts Code burner at-a-glance . . .

1

Manual gas valve (with two test tappings)

Gas supply entrance (gas train size): — 1” NPT or 1¼” NPT

(gas train size depends on input and application)

Supply pressure: 5” w.c. min; 14” w.c. max; natural gas or propane

2

Gas pressure regulator

3

Gas pressure regulator vent port (fitted with fixed orifice; vent to outside where

required by applicable codes)

4

Low gas pressure switch — manual reset

5

Automatic gas valve

6

Junction box with terminal strip

7

Automatic gas valve (two-stage regulating diaphragm valve)

9

High gas pressure switch — manual reset

10

Manual gas valve

10a

Burner gas manifold pressure test port, 1/4” NPT

11

Union

12

Orifice nipple (burner gas orifice plug located inside)

13

Burner gas connection, 1” or 1¼” NPT

14

Air tube (flange omitted for clarity), with powder coat paint finish

15

Flame rod/insulator assembly

16

Combustion head assembly

17

Gas saddle connection gasket

18

Gas manifold

19

Ignition electrode/insulator assemblies

20

Motor (with permanently-lubricated bearings and thermal overload protection)

21

Hinged burner flange door — for access and removal of combustion head/gas

manifold assembly

22

Ignitor (Carlin Model 41000 solid state electronic ignitor — 14,000 volts, continu-

ous duty rated)

23

Hinged cover plate (for access to blower wheel & electrodes)

24

Airflow proving switch — Prevents burner from firing if air is not moving

25

Air damper — Only a single adjustment required for setting combustion air; see

page 9 for starting setting based on input

26

Door interlock switch — prevents burner operation if flanged door is open

27

Primary control — Carlin Model 60200FR microprocessor-based interrupted

ignition flame supervisory control (flame rectification); Flame current test jack is

located to right of control terminal strip

28

Burner junction box (installer electrical entrance)

29

Time delay relay (8-second)

Replace Instruction manual content:

This page replaces Instruction manual page 4.

Advertising