Model 601GAS burner — Instruction manual — Supplement – Massachusetts Code

Carlin part number MN601GASM Rev. 05/01/07

–  –

Where appliance instructions differ from this manual, follow the appliance instructions.

Replace Instruction manual content:

This page replaces Instruction manual page 19.

5. Perform checkout procedures • fill out certificate

(continued)

Verify burner/appliance operation

(Massachusetts Code burners)

Check burner/appliance/controls operation

Test operating and limit controls on appliance as specified in appliance

instruction manual.
Check operation of the 60200FR primary control by forcing Latch-up (three

consecutive lockouts during the same call for heat): Close the main manual

gas cock. Temporarily jumper the low gas pressure switch. Then cycle

the burner. Press the reset button to reset when the 60200FR control

locks out on flame failure. Do this two times and the control should enter

Latch-up. See page 17 to reset control. Remove the jumper from the low

gas pressure switch.

Verify that the burner starts in low fire, then goes to high fire after 8

seconds. (The time-delay relay delays power to the gas valve second

stage for 8 seconds.)

Check the airflow switch

Cycle the burner off with the appliance controls. Then turn off power to

the appliance. Remove both of the sensing lines from the airflow switch by

loosening the plastic sealing nuts and pulling the aluminum sensing tubes

out of the socket.

With the sensing lines removed, turn on power to the appliance and set the

controls to call for heat. Watch the manometer on the manual gas valve outlet

pressure tap. After the control performs its pre-purge, it will try to turn on

the gas valves. The gas valves should not open with the airflow sensor lines

removed. Set the controls to stop the call for heat and turn off power to the

appliance. If the airflow switch operates correctly (gas valves don't open),

continue with normal operation. If the airflow switch fails to operate correctly,

replace the switch and retest.

NEVER attempt to adjust the air pressure switch setting. This

could allow unsafe operation of the burner, resulting in potential of
severe personal injury, death or substantial property damage.

Check high gas pressure switch

Cycle the burner off with the appliance controls and turn off power to

the appliance/burner.

Attach a manometer to the manifold-side manual gas valve test port.
Turn on power and cycle the burner on with the appliance controls.
Measure the manifold gas pressure with the manometer.
Set the high gas pressure switch to a pressure less than actual manifold

pressure. The high gas pressure switch should shut the burner down.

Replace the switch if necessary.

Turn off power to the appliance/burner; remove the manometer and

replace the plug in the gas valve test port. Reset switch.

Check low gas pressure switch —

Cycle the burner off with the appliance controls and turn off power to

the appliance/burner.

Close the main manual gas valve.
Cycle the burner on.
The low gas pressure switch should shut the burner down. Replace the

switch if necessary.

Turn off power to the appliance/burner.
Open the main manual gas valve.
Reset low gas pressure switch.

q

q

q

q

q




q





Check flange door switch

Cycle the burner off with the appliance controls and turn off power

to the appliance/burner.

Remove the nuts securing the hinged flange and swing the flange

open.

Attempt to cycle the burner with the appliance controls.
The flange door switch should prevent the burner from operating.

Replace the switch if necessary.

Close the flange door and replace the nuts.

Verify burner operation

Start and stop the burner several times, allowing the primary

control to sequence through normal operation. Verify correct

operation of burner and controls throughout, including the burner

door switch and high and low gas pressure switches.

Verify vent system operation

Verify vent is operating correctly and flue products are properly

exhausted from building.
Check operation of barometric damper and spill switch.
If the building contains any exhaust fans or conditions that could

affect vent performance, check burner/appliance/vent operation

with exhaust fans (or other conditions) operating.

Prepare the burner for normal operation

Cycle burner off with appliance controls. Then turn off power to

the appliance.
Close the main manual gas valve.
Verify all components and wires are in place and burner is ready

for operation.
When all tests and checks are completed, restore the burner and

appliance to normal condition for operation.
Start the burner again to verify proper operation before leaving.

Train the user

Train the user to operate the burner and appliance under normal

conditions. Explain procedure to shut down burner/appliance

when required.
Review the user information manual (and the appliance instruc-

tions) with the user.
Verify the user is aware of all procedures specified in the

manual.
Verify user will not store or use combustible liquids or materials

or contaminants in the vicinity of the burner/appliance.

q

q

q

q

q

q

q

q

q

q

q

q

q

q