17 – start-up & operation, Service & troubleshooting, Burner (control) will not come on – Carlin 301CRD User Manual

Page 17: Repeated fl ame failures ( fl ashing red led ), Control locks out after tfi ( red led on )

Advertising
background image

Model 201CRD & 301CRD 240-VAC Advanced oil burners — Instruction manual

Carlin part number MN2301A Rev. 10/21/10

– 17 –

Start-up & operation

Do not start the burner if the combustion chamber contains

oil or oil vapor.

Per UL requirements, the control will not turn on if the cad

cell senses fl ame during the self-test. If the cad cell sees

light, the control will remain in self-test mode until the cad

cell no longer senses light (fl ame). The amber LED will re-

main on, but blink off momentarily

every 3 to 4 seconds.

Check 50240 control label for trial for ignition (TFI)timing.

Model 50240 diagnostic LED’s

– Red OFF

– Red ON

– Red FLASHING

– Amber OFF – Amber ON – Amber FLASHING

– Amber BLINKING (blinks off momentarily every 3 to 4 seconds)

Service & Troubleshooting

Burner (control) will not come on

No power to control

• Check line voltage to the control (at least 102

VAC

).

• Check all electrical connections.

Control is in lockout

• Red LED will be on. Press the reset button for 1 sec-

ond.

• If the control returns immediately to lockout, The Safety

Monitoring Circuit may have detected an internal con-

trol problem. Replace the control.

CAD cell seeing light

• Amber LED blinks off each 3 to 4 seconds. Remove

one yellow lead from FF terminal on the control.

If the amber LED remains on with a wire detached,

the control is defective.

If

amber

LED goes off , control is OK, and:

• light is leaking into the burner housing,

OR

• CAD cell is defective,

OR

• there is a problem with the CAD cell wiring or holder.
• If appliance was recently shut down, CAD cell may

see residual hot spots in chamber.

To

troubleshoot:

Check CAD cell by unplugging it and measuring

the resistance across its pins: dark resistance at

least 50

KOHMS

; room light resistance less than

10

KOHMS

. Replace if necessary. If the CAD cell

functions properly, reinstall the cell and close the

burner housing.

Check for stray light by measuring the CAD cell

resistance looking into the inactive combustion

chamber. It should read at least 50

KOHMS

.

Repeated fl ame failures ( fl ashing red LED)

Check

for:

• CAD cell is defective.

• Air leaking into oil line causing fl ame out — Check oil line

connections and fi lter gasket.

• Defective nozzle causing fl ame to be erratic — Change

nozzle.

Excessive

airfl ow or draft causing fl ame to leave burner

head — Check for proper air shutter setting and draft.

• Excessive back pressure causing fl ame to be erratic —

Check appliance and fl ue for sooting/plugging.

Control locks out after TFI ( red LED on)

Check

for:

• No oil to burner — Check oil supply, fi lter, lines.

• Shorted electrodes — Inspect for cracked porcelain and

replace as needed.

• Poor spark — Check electrode spacing and condition per

burner manual. Replace or realign if necessary.

• Nozzle clogged — Replace nozzle.

Airfl ow too high — Check air shutter setting.

• Ignitor module defective — Replace if no spark.

• CAD cell defective.

• Oil valve stuck in closed position.

• Check wiring connections.

Power ON

Open all manual oil line valves. Close the line switch. (If Red light

turns on constant

, control is in lockout. See below to reset.)

Self-test 1

Each time the limit circuit sends power to the black wire, the con-

trol performs a “boot-up” test to verify internal operation. About 4

seconds after power application, the amber LED turns on. The test

continues for about 6 more seconds. If the test fails, the control

turns the amber LED off and repeats this test sequence until suc-

cessful. (This test occurs on every call for heat cycle if burner is

operated by a limit control (terminals “T-T” jumpered).

Stand-by

(Thermostat circuit open, limit circuit closed) If Self-test 1 is

successful, amber LED turns off and control waits for thermostat

circuit to close.

Call for heat Set thermostat to call for heat. Thermostat circuit must close (and

black wire must receive power from the limit circuit).

Self-test 2

The amber LED turns on. For the fi rst 3 to 4 seconds, the control

performs a self-test. If the cad cell senses fl ame, the control

repeats this test until fl ame is no longer detected. During this time,

the amber LED remains on, but blinks off momentarily

every 3

to 4 seconds. If the control detects motor contacts closed, lockout

occurs.

Burner on

After the self-test, amber LED turns off. The ignitor starts, fol-

lowed 1 second later by the motor. The electronic time delay relay

allows the oil valve to open 4 seconds later.

TFI

The cad cell must sense fl ame within the TFI time limit (trial for

ignition). After cad cell senses fl ame, the ignitor stays on another

10 seconds (fl ame stabilization period).

Run

The burner continues fi ring during call for heat if the cad cell

senses fl ame. LED’s are off during normal running.

Lockout

If cad cell does not sense fl ame within 15 seconds after burner

starts, lockout occurs. The control turns the red LED on constant,

and closes the alarm contact.

To

Reset

Push in and hold reset button for 1 second, then release.

Latch-up

If the control locks out 3 times during a single call for heat, latch-

up occurs. The control turns on both the amber and red LED’s

constant. You must use the special procedure below to reset the

control after latch-up.

Reset after latch-up — Only a qualifi ed service techni-

cian should attempt to reset the control after latch-up. The

problem that caused the repeated burner problems must be

corrected before returning the burner to normal operation.

Push in and hold the reset button for about 10 seconds. The

amber and red LED’s will begin to fl ash alternately.

After the LED’s begin fl ashing, continue holding the reset button

for about another 20 seconds. The LED’s will turn off. Release the

reset button and the control will restart. (Releasing the button be-

fore the LED’s turn off will cause the control to remain in latch-up.)

The 50240 control will not reset from lockout or latch-up if power is

interrupted.

Flame failure If the cad cell loses fl ame signal during operation (after the TFI),

the red LED fl ashes. The burner shuts off within 2 seconds. Re-

cycle: Control waits for 65 seconds (with red LED fl ashing), then

begins again at Self-test 2. Red LED goes off

.

End cycle

Set thermostat (or aquastat) to stop call for heat. The burner shuts

off within 2 seconds after end of call for heat.

Stand-by

Control remains in stand-by mode until limit circuit sends power to

the black wire (call for heat).

Advertising