Troubleshooting, Warning – Carlin G3B User Manual

Page 19

Advertising
background image

Model G3B Gas burner — Instruction manual

Carlin part number MNG3B Gas Rev. 03/17/09

19

7. Troubleshooting

Problem

Possible
cause

Corrective action

WARNING

These procedures must only be performed by a qualifi ed service
technician. Use care when performing tests on electrically or
mechanically live parts. Disconnect power to burner/appliance and close
main manual gas valve when removing components for service. Failure
to comply could result in severe personal injury, death or substantial
property damage.

Burner motor will
not start

120 V power

Check 120 V at terminal strip. L1 - L2

Check limit/operative circuit.

24 V circuit

Check that 24 V thermostat/circuit is calling for heat.

Check transformer output. Each “T” on terminal strip should read
approx. 24 volts to “G” ground.

Incorrect wiring

Check all fi eld and factory wiring.

Bad motor relay

Check 24 V at motor relay. Relay should click (pull-in) on call for heat.

Check continuity across contacts (N.O.) or each side of contact to L2 on
terminal strip should read 120 volts.

Bad motor

If motor relay is good (see above) and wiring is correct, disconnect the
motor leads and power the motor directly with 120 V to check motor
operation.

Bad primary
control

If all above tests prove negative replace control.

Burner pre-
purges for 34
seconds but
does not light
(continued on
next page)

Incorrect air
setting

For initial light-off set air throttle according to desired input.

Wrong orifi ce
size

Check orifi ce drill size.

Manual gas shut-
off valve closed

Check supply line gas cock and manual shut-off valve on combination
gas valve.

Manifold
pressure

Adjust regulator to 3.5 W.C. for natural gas and propane.

Gas valve not
opening

Check for 24 V valve coil during TFI. Indicator light should also be on.

Line pressure in excess of 14.0 W.C. can damage valve.

Motor end switch
not making

Check motor end switch.

Disconnect the two red leads in the panel coming from the motor end
bell. Check continuity during pre-purge. End switch will not activate if
motor is not running up to speed.

Hot surface
ignition element
damaged

Element normally glows red within 20 seconds during pre-purge. Use
fl ame mirror to visually inspect.

Check for 120 V at rear of ignitor assembly during pre-purge.

If visual inspection cannot be done, remove element and power directly
with 120 V. Replace element if it does not glow red within 45 seconds.