Prepare burner – Carlin 102CRD-99FRD-100CRD User Manual

Page 13

Advertising
background image

Model 99FRD, 100CRD, & 102CRD oil burners — Instruction manual

Carlin part number MN99102 Rev. 10/21/10

– 13 –

Figure 15 Two-line fuel system

Table 4

Two-line fuel system maximum lengths for 3/8”
and 1/2” OD copper tubing distribution. Use only
for burners equipped with Suntec fuel units. See
fuel unit data sheet for any other fuel unit.

Perform checkout procedures

Verify before starting burner:

Should overheating or an emergency occur, immediately:

• Shut off oil supply line valve.

• Under some circumstances power should remain on for
water pumps or blowers. Determine proper response before
attempting start-up.

• If burner fails ignition on several attempts, use burner
blower to purge appliance chamber before restart.

Checklist

Burner/appliance installed per appliance instruction manual?

Burner nozzle and head positioning bar verifi ed against Table 1, page
3, or appliance manufacturer’s instructions?

Burner/appliance installed per all applicable codes?

Installation site has adequate combustion/ventilation air openings and
vent system?

Fuel supply line in good condition and sized/designed correctly?

Oil tank has oil and oil line valves are open.

Wiring installed per burner/appliance instructions?

Burner, appliance and all components inspected and in good condition?

3. Prepare burner

(continued)

Two-line fuel system requirements

See Figure 15 and Table 4. Use Table 4 only for burners equipped with
Suntec fuel units. For burners using other fuel units, read the fuel unit
manufacturer’s data sheet to determine maximum lengths and lifts.

The standard burner fuel unit is a single-stage, 3450-RPM oil pump. Use
this fuel unit only on two-line oil systems that do not exceed the total
tubing lengths allowed in Table 4 (for Suntec fule units only). For longer
systems (or where lift exceeds 10 feet), replace the one-stage fuel unit
with a two-stage unit.

Always size fuel lines using an oil fl ow rate based on the fuel unit gearset ca-
pacity, not the burner fi ring rate. See fuel unit data sheet for information.

Install the fuel unit bypass plug when connecting to a two-line

system. The plug is shipped in a bag attached to the fuel unit,
along with a fuel unit data sheet.

Advertising