4.2

UD10-DCU Wired to GT3000 Detector with Sensor Termination Box

NOTE 1

GROUND THE SHIELD AT THE DISPLAY

UNIT END ONLY.

NOTE 2

HOUSINGS MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

SEE NOTE 1

A2512

RED

BLACK

GT3000

GAS DETECTOR

SENSOR TERMINATION BOX

RED

RED

BLA

CK

BLACK

GREEN

Sensor Connector

Power Supply Connector

LON Connect

or

J4

J3

J7

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

J4-1

J4-2

J4-3

J4-4

J4-5

J7

-6

J7

-5

J7

-4

J7

-3

J7

-2

J7

-1

SHIELD

2 B COM

2 A COM

SHIELD

1 B COM

1 A COM

J3-1

J3-2

J3-3

J3-4

J3-5

J3-6

UD10

DISPLAY UNIT

SW3

J2

ON

orientAtion

The device must be mounted in a vertical position only,

with the GT3000 pointing down.

liVe mAintenAnce

noTe

The sensor module on the GT3000 Gas Detector
can be hot swapped, i.e. replaced without
removing power or de-classifying the area. To
replace a GTX Transmitter connected to the
UD10-DCU with a new transmitter or a different
detector type, the area

must be de-classified.

noTe

Removing the sensor module with power applied
will result in a fault condition until a new sensor
module of the same type is installed. When
replacing an oxygen sensor, this action will also
result in an alarm condition as the decreasing
4-20 mA signal passes through the alarm range.
Inhibit response devices to prevent unwanted
actuation.

For complete information regarding sensor replacement

with the GT3000 Gas Detector, refer to the GT3000

instruction manual number 95-8616.

Advertising