Appendix m, Wiring – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual
Page 63

4.2
95-8656
M-1
AppenDix m
UD10-DCU with mODEL 505 TRaNSmITTER / CgS SENSOR
noTe
For complete information regarding the Model 505 Transmitter, refer to instruction manual 95-8472.
WirinG
4000
3500
3000
2500
2000
1500
1000
500
0
18
19
20
21
22
23
24
25
26
27
28
29
30
Power Supply Voltage
Dist
ance in f
t.
UD10-DCU with PIRECL/OPECL/NTMOS/CGS
12
14
16
18
AWG
Wire Size
Notes: Maximum cable length from power source to UD10 is 2000 feet.
Maximum cable length from UD10 to CGS sensor is 500 feet
(using 16 AWG cable minimum).
UD10
DISPLAY UNIT
MODEL 505 TRANSMITTER
CGS
SENSOR
A2519
–
SIG
RED
SENSOR
WHT
BLK
+
NOTE UD10 HOUSING MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
Sensor Connector
Power Supply Connector
LON Connect
or
J4
J3
J7
24 VDC
–
24 VDC
+
SHIELD
24 VDC
–
24 VDC
+
SHIELD
SHIELD
C
ALIBR
A
TE
24 VDC
–
4-20 mA
24 VDC
+
J4-1
J4-2
J4-3
J4-4
J4-5
J7
-6
J7
-5
J7
-4
J7
-3
J7
-2
J7
-1
SHIELD
2 B COM
2 A COM
SHIELD
1 B COM
1 A COM
J3-1
J3-2
J3-3
J3-4
J3-5
J3-6
SW3
J2
ON
UD10-DCU Wired to Model 505 Transmitter/CGS Sensor