Det-Tronics GTS Sensor Module SAFETY MANUAL User Manual

Page 3

Advertising
background image

1.1

95-8685

3

INSTALLATIoN

NOTE

For complete information regarding performance,
installation, operation, maintenance and
specifications of the GT3000 Series, refer to
instruction manual 95-8616.

No special or additional detector installation

requirements exist above and beyond the standard

installation practices documented in the GT3000

instruction manual.

The operating temperature range for the Safety Certified

GT3000 depends on the specific sensor being used.

Refer to the GT3000 instruction manual for details.

Other environmental operating specifications are

applicable as published in the general specifications

section in the GT3000 instruction manual.

The GT3000 operating power distribution system

should be designed and installed so the GT3000

terminal voltage does not drop below 12 Vdc when

measured at any specific location. The external system

providing power to the GT3000 must have over-voltage

protection that ensures supply voltage does not exceed

30 Vdc.

NOTE

All safety functions of the GT3000 are active
within 150 seconds of power-up without any user
action required.

CoMMoN MISUSE SCENARIoS
Refer to the Installation and Maintenance sections of

the instruction manual for information on avoidance and

resolution of common misuse scenarios. Applications

to avoid include the following:
- Locations where impact or other excessive

mechanical stress is likely.

- Locations where regular contamination from debris,

trash, snow, mud, etc. is likely to contact the sensor.

- Horizontal mounting of the GT3000 (see DEVICE

MOUNTING ORIENTATION section of the GT3000

Instruction Manual).

- Locations where sensor cross-sensitivity to other

gases will be a problem (see Appendix A of the

GT3000 Instruction Manual for details).

NOTE

If the user suspects that damage or misuse has
occurred to the GT3000, a full proof test shall be
performed.

START-UP AND CoMMISSIoNING

Commissioning Personnel
The Safety Certified GT3000 Toxic Gas Detector can be

commissioned by any qualified person with knowledge

of gas detection instruments and the configuration

device being used.

Refer to the Installation and Calibration sections

provided in the GT3000 instruction manual.

Configuration
A HART handheld device can be used to monitor

internal status or to modify the factory settings of the

GT3000. Refer to the GT3000 HART Communication

section of the instruction manual for guidance on using

HART communication.

NOTE

Prior to device configuration all alarm outputs
must be bypassed. The device is not safety
certified during configuration change activities.

NOTE

All configuration changes to the GT3000 must be
verified by the user via a proof test, power cycle
and re-check of settings, or other appropriate
method.

Configuration Protection
Upon completion of installation and commissioning, it

is required that the user password-protect the GT3000

safety related parameters that are accessible via HART

in order to prevent accidental or deliberate change

of configuration data during normal operation. To

password protect the GT3000, the user must set the

write-protect function to “on” and enter an 8 character

password.

The user will be required to disable write protect

prior to any future configuration changes, and must

re-enable write protect upon completion of these

changes to ensure that HART communication remains

non-interfering.

Advertising