CERTIFICATIoN AND FAILURE RATE DATA
All Safety-Certified GT3000 Toxic Gas Detectors are

certified compliant to:

IEC61508: 2010
Type B Element
Systematic Capability: SIL 2 certified
HFT: 0
Low Demand Mode
PFDavg should be calculated for any safety instrumented

function using the GT3000. (Refer to FMEDA report for

necessary information, including DU rate.)
Safety Accuracy:

±10% of applied gas

concentration.

Safety Response Time: Depends on sensor module

being used. Refer to GT3000

instruction manual for details.

Product Life:

3-5 years, based on

manufacturer data.

All failure rate data for SIL verification is in the FMEDA

report, which is available upon request.

ADDITIoNAL CERTIFICATIoNS
FM, CSA, ATEX, IECEx, CE, and others.

Refer to the GT3000 Instruction Manual for details.

For complete information regarding performance,

installation, operation, maintenance and specifications

of the GT3000, refer to instruction manual 95-8616.

TERMS AND DEFINITIoNS

AMS

Asset Management System

FMEDA

Failure Mode Effects and Diagnostics

Analysis

HART

Highway Addressable Remote

Transducer

HFT

Hardware Fault Tolerance

LFL

Lower Flammable Limit

V/V

Percent by volume

PFD

Probability of Failure on Demand

(Probability of Dangerous Failure)

PFDavg

Average Probability of Failure on

Demand

SFF

Safe Failure Fraction

SIF

Safety Instrumented Function

SIL

Safety Integrity Level

SIS

Safety Instrumented System

GT3000

Electrochemical Toxic Gas Sensor

(consists of one GTX Transmitter and

one GTS Sensor Module)

Detector Electronics Corporation

6901 West 110th Street • Minneapolis, Minnesota 55438 USA

Operator: (952) 941-5665 or (800) 765-FIRE

Customer Service: (952) 946-6491 • Fax (952) 829-8750

http://www.det-tronics.com • E-mail: [email protected]

Specifications subject to change without notice.

Det-Tronics, the DET-TRONICS logo, and FlexVu are registered trademarks
or trademarks of Detector Electronics Corporation in the United States,
other countries, or both. Other company, product, or service names may be
trademarks or service marks of others.

©Copyright Detector Electronics Corporation 2012. All rights reserved.

R

EG

IST

ERE

D BY UL AN

D B

SI

NO

. A2305 • NO. 2582

6

ISO 9001

RE

GIS

TERED FIRM

R

EG

IS

TERED FIR

M

Failure Category

l

sd

l

su

2

l

dd

l

du

SFF

3

GT3000 Analog Output with

H

2

S Sensors

0

199

3136

275

92.4%

GT3000 Analog Output with

O

2

Sensor

0

243

3123

141

96.0%

IEC 61508 Failure Rates in FIT

1

1

FIT = 1 Failure / 10

9

Hours

2

It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.

3

Safe Failure Fraction needs to be calculated on (sub)system level.