down, the distance from the detector to the designated
level would be 10 feet (3 meters). Because of the nomi-
nal 90 degree cone of vision, the detector covers a cir-
cular area having a diameter of approximately 20 feet (6
meters). A simple layout of the area to be covered will
show the number of detectors required to completely
supervise the designated area.

DETECTOR MOUNTING AND WIRING

All wiring must comply with local codes, regulations,
and ordinances.

1. Refer to Figure 8. While holding the detector barrel,

remove the four hex screws from the top of the junc-
tion box. Carefully lift the detector barrel and
unplug P1 from the terminal block board recepta-
cle. Set the detector barrel aside.

4

SYNCHRONOUS

DETECTOR

SENSOR

1

CHANNEL

AUTOMATIC

GAIN

CONTROL

B0578

SENSOR

2

CHANNEL

AMPLIFIER

AMPLIFIER

FAULT

DETECTOR

POWER

SUPPLY

RATIO

"AND"

STARTUP

DELAY

THRESHOLD

DETECTOR

FAULT

OUTPUT

ALARM

OUTPUT

Figure 7—Block Diagram of U7099 Signal Processing Sequence

B0913

JUNCTION BOX

HEX SCREWS (4)

SWIVEL

DETECTOR BARREL

SENSOR CAP

O-RINGS

SENSOR/CONTROLLER MODULE

SWIVEL ADJUSTMENT SCREW

P1

Figure 8—U7099 Assembly