Startup procedure, Important – Det-Tronics U7099 Dual Frequency IR Detector/Controller User Manual

Page 6

Advertising
background image

2. Mount the junction box in the desired location. See

Figure 3 for mounting dimensions.

3. Connect the input power and relay contact leads

through the conduit to the terminal blocks. Figures
4 and 5 show the wiring diagrams for the standard
U7099 and the U7099 with an Auxiliary Fire relay,
respectively. Figure 9 shows the terminal block and
end of line resistor locations. Figure 10 shows typi-
cal system wiring using two standard U7099
Detector/Controllers with an end of line resistor
installed.

IMPORTANT

An 8.25 kilohm end of line resistor is installed
between terminals A and B on standard U7099
Detector/Controllers for use if required (see Figure
4). If an end of line resistor is not required, remove
the resistor from the terminal block (see Figure 9 for
location). With the end of line resistor installed, there
will be continuity between the Fire relay common
(terminal 5) and the Fault relay common (terminal 8).

4. Check all field wiring to ensure that the proper con-

nections have been made. If conduit is used, pour
the conduit seals and allow them to dry.

5. Plug P1 from the detector barrel assembly into the

terminal block board receptacle.

6. Replace the four hex screws attaching the detector

barrel to the junction box.

7. Loosen the swivel adjustment screw to position the

detector. Tighten screw when desired position is
obtained.

CAUTION

Do not rotate swivel more than 360 degrees.
Swivel contains internal wires that can be dam-
aged if rotated more than 360 degrees.

8. Perform the “Startup Procedure.”

STARTUP PROCEDURE

The following startup procedure should be performed
after installation of the equipment is complete.

1. Disable any extinguishing system connected to the

unit. Connect external annunciation equipment to
the U7099 relay contacts.

2. Turn on the input power to the U7099 (allow one

minute warmup).

3. Hold the Det-Tronics Model W868 Test Lamp

against the viewing window of the detector for 5 to
10 seconds.

4. The alarm relay in the U7099 energizes the external

annunciation equipment.

5. Turn off the IR source.

6. If the U7099 fails to pass the test, refer to the

“Troubleshooting” section of this manual.

7. When all detectors have been checked for normal

operation, they should be checked to see if they
adequately cover the protected areas for complete
fire protection.

5

95-8272

B0914

CIRCUIT

PROTECTION

FUSES

250 VOLT

1/4 AMP

8.25K END OF LINE RESISTOR - REMOVE IF NOT REQUIRED

Figure 9—Terminal Block

7

8

9

B

A

8.25K
0.25W

6

5

4

3

2

1

7

8

9

B

A

6

5

4

3

2

1

FIRE

FAULT

FIRE

FAULT

U7099

U7099

FIRE ALARM

PANEL

+

+24 VDC

POWER SUPPLY

+

+

+

A1689

Figure 10—Typical U7099 System Wiring Using End of Line Resistor