Main power – ElmoMC Gold Line Digital Servo Drives-Gold Duo User Manual
Page 26

Gold Duo Installation Guide
MAN-G-DUOIG-E (Ver. 1.500)
||Main and Auxiliary Power
26
6.3.2.
Main Power
Pin
Signal
Function
Cable (Wires)
J13/1
VP+
Pos. Power input
DC Power
J13/2
VP+
Pos. Power input
DC Power
J13/3
PR
Power return
DC Power
J13/4
PR
Power return
DC Power
J13/5
PE
Protective earth
DC Power
5-Pin Phoenix 5 mm Pitch ‘HC’
5-Pin Phoenix Plug-in
Connector
Table 5: Main Power Pin Assignments
Connect the DC power cable to the VP+ and PR terminals on the Main Power Connector.
To connect the DC power supply:
1.
The source of the 12 to 195 VDC power supply must be isolated.
2.
For best immunity, it is highly recommended to use twisted and shielded cables for the DC
power supply. A 3-wire shielded cable should be used. The gauge is determined by the
actual current consumption of the motor.
3.
Connect the cable shield to the closest ground connection near the power supply.
4.
Connect the PE to the closest ground connection near the power supply.
5.
Connect the PR to the closest ground connection near the power supply.
6.
Before applying power, first verify the polarity of the connection.