Junction box installation, Occupancy sensor – ETC Unison Paradigm Occupancy Sensor User Manual

Page 3

Advertising
background image

E T C I n s t a l l a t i o n G u i d e

Occupancy Sensor

Occupancy Sensor Installation Guide

Page 3 of 8

Electronic Theatre Controls, Inc.

Junction Box Installation

Step 2:If you are installing the sensor in series with other sensors or stations

(continuing the data run), use the provided LinkConnect pigtail, ESD ground
pigtail and WAGO connectors to make the terminations. If you are not
continuing the data run
, proceed to step 3.

Step 3:Orient the smooth side of the mounting plate to the junction box and pull the

Belden 8471 and the 14 AWG (2.5mm

2

) ESD ground wire from the junction

box through the provided holes near the center of the mounting plate.

Step 4:Secure the mounting place to the junction box using the screws provided (both

short and long screws are included for convenience).

Step 5:Strip each wire 5/16” (8mm) and terminate the white, black, and green (ground)

wires to the terminal block located on the sensor control board. Torque each
termination to 3.1-3.5 in-lb.

a: Terminate the white incoming wire to terminal A.
b: Terminate the black incoming wire to terminal B.
c: Terminate the green wire to the ground terminal.

Step 6:Attach the sensor to the mounting plate by aligning the tabs on the sensor with

the slots on the mounting plate, then twist clockwise until the two are locked
into place.

terminate

wires here

Step 1:Pull the Belden 8471 (or

equivalent) and 14 AWG
(2.5mm

2

) ground wire to the

junction box.

install

ed control

wire

installed control wire to next stati

on

sensor pigtail

a: Strip 3/16” (5mm) of insulation from each installed LON wire.
b: Open the three terminal levers on a WAGO connector and

insert the installed (typically black) Belden 8471 LinkConnect
wire, the black lead from the sensor pigtail, and the
continuing Belden 8471 (typically black) wire into the
terminals.

c: Close the levers onto the wires.
d: Repeat the above for the installed (typically white) Belden

8471 LinkConnect wire and the remaining pigtail from the
sensor, as well as the ESD ground wires using a new WAGO
connector for each termination type.

Advertising