Rack Cabling Access

ESR3 racks have removable top and bottom access panels.

Conduit Connections

Step 1:

Remove the desired access panel from the rack.

Step 2:

Cut access holes in the top and bottom access panels.

Step 3:

Install your cabling into the holes.

Step 4:

Re-install the access panel so that there are minimal air gaps.

See “Sealing Rack

Air Leaks” on page 28.

for more information

.

Trunking or Wire Trough Connections

Step 1:

Remove the desired access panels.

Step 2:

Cut suitable openings to mate with the trunking or trough using a jigsaw or

hacksaw.

Step 3:

Reinstall panel on to rack

Step 4:

Install a fiche paper lining or grommeting material in the access panel opening.

Step 5:

Position the trunking or wire trough above the prepared opening.

W A R N I N G :

Cutting holes in the rack plates in situ may introduce metal debris into the

dimmer cabinet.

N o t e :

Wire openings must have fittings or linings to protect cable insulation from

damage by sharp metal edges.

Figure 8: ESR3 access panels