6.

Address Assignment

The device offers two different types of AS-i addresses:
The safety relevant (single) AS-i address is the target address for the device
through which it receives the signal for the safe release of the output. This ad-
dress is not used for communication; the device only uses it to listen to ongoing
communications.
This address can only be programmed if the switch is set to PRG.
The device uses the non-safety relevant (A/B) AS-i address to communicate with
the master in order to exchange diagnostics data (I1 …I3, 1.Y1) and control sig-
nals (Alarm LED).
This address can only be programmed if the switch is set to RUN.

6.1

Programming of the safety relevant AS-i address
1.

Set device switch to PRG.

2.

Set desired address by using the hand-held addressing device or AS-i Mas-

ter.

3.

Check programmed address by using the hand-held addressing device or

AS-i Master.

4.

Check slave’s ID code by using the hand-held addressing device or AS-i

Master. The code should be set to “F”.

5.

Check slave’s ID1 code by using the hand-held addressing device or AS-i

Master. Code should be the same as the tens-digit of the address.

6.

Check slave’s ID2 code by using the hand-held addressing device or AS-i

Master. The code should be the same as the ones-digit of the address.

7.

Check slave’s IO code by using the hand-held addressing device or AS-i

Master. The code should be “7”.

8.

If the settings in steps 3 to 7 were correct continue with step 9. Otherwise

repeat, starting with step 1.

9.

Set the switch on the device to RUN.

.

6.2

Programming of the non-safety relevant AS-i address
This address can be programmed by using the hand-held addressing device or
AS-i Master when the switch is set to RUN.

Warning!

The correct safety function of the device must be verified once installed within the pro-
tected machinery!