Operating Instructions Enabling Switch ZSM

Correct use

The EUCHNER enabling switch is a manually oper-

ated command switch, which allows work to be car-

ried out in the danger area of automated production

systems in the manual operating mode. This mode

must be secured with a lockable selector switch

according to EN 60204, part 1.
The enabling switch must be logically gated with the

machine control system in a manner that ensures

compliance with the requirements applicable to

safety circuits according to VDI 2854 and/or EN ISO

10218-1. Under the conditions specified therein, the

enabling signal may cancel the protective action of

moving safety guards. Authorized operating person-

nel may then enter the danger area:

f

for setting up

f

for observing work sequences

f

for maintenance.

Important:

f

The user is responsible for the integration of the

device in a safe overall system. For this purpose

the overall system must be validated, e.g. in ac-

cordance with EN ISO 13849-2.

f

If the simplified method according to section 6.3

EN ISO 13849-1:2008 is used for validation, the

Performance Level (PL) may be reduced if several

devices are connected one after the other.

f

The enabling switch user must assess and docu-

ment remaining risks.

f

If a product data sheet is included with the product,

the information on the data sheet applies in case

of discrepancies with the operating instructions.

Incorrect use

The enabling signal must not be simulated by fixing

the switching contact in the enabling switch.
Attachments, such as key-operated rotary switches,

buttons, etc., are not allowed to be used for safety

tasks.
The stop button on enabling switches with plug

connector must not be used as an emergency stop

device according to IEC 60204-1.
It is only allowed to used a hard-wired electrome-

chanical emergency stop device for shutting down

in an emergency.

General

If 2-channel evaluation is used with monitor-

ing for same contact state, category 3 as per

EN ISO 13849-1 is attained.
Depending on the version, buttons, a key-operated

rotary switch and a stop button, etc., provide ad-

ditional functionality.

Function

Stage 1: Off function, pushbutton not pressed
Stage 2: Enabling function, pushbutton pressed to

center position (actuating point)

Stage 3: Off function, pushbutton pushed to end

stop

The enabling function is canceled by releasing the

pushbutton or pressing it beyond the actuating point.

The enabling function does not reactivate when

returning from stage 3 to stage 1.

Safety precautions

Enabling switches fulfill a personal protection func-

tion. Incorrect use or tampering can lead to severe

injuries to personnel.

All the safety and accident prevention regu-

lations for the specific application, e.g.

guidelines of the employers liability insurance

associations, safety requirements of the VDI

(EN ISO 10218-1, VDI 2854), EN 60204,

EN 12100, EN ISO 13849, EN 61062,

DIN VDE 0106 part 100, etc., must be ob-

served.

Electromechanical enabling switches/devices

are to be logically gated with the control system

in a manner that ensures compliance with the

requirements applicable to safety circuits ac-

cording to EN ISO 10218-1, DIN EN 60204-1,

EN ISO 13849-1, DIN EN ISO 11161 and

VDI 2854.

No commands for potentially hazardous condi-

tions are allowed to be initiated with enabling

switches alone.

The safety function of enabling switches must

not be bypassed (bridging of contacts), manipu-

lated or otherwise rendered ineffective.

The enabling switch must be protected against

attempts by the operator to bypass its function.

Enabling switches may be used only by au-

thorized persons who can recognize hazards

in time and who are able to take appropriate

action immediately.

Every person present in the danger area must

carry his/her own enabling switch on his/her

person.

Mounting, electrical connection and setup only

by authorized personnel.

Mounting

A suitable holder must be used for enabling

switches.

Electrical connection

In safety circuits, both contacts on the enabling

switch must be evaluated separately (2-channel)

(Figure 1).

In the installation of a system, the cables and

wires used (except earth conductors) that can

be touched without opening or removing a

cover, or are laid on conductive parts external

to the device, must be either double insulated

or have reinforced insulation between core and

surface, or be surrounded by a metal sheath

of adequate current-carrying capacity in case

of a short between core and sheath.

For use and operation as per the

require-

ments, a power supply with the feature “for use

in class 2 circuits” must be used.

Hazards due to crushing or cutting of the connec-

tion cable must be prevented by suitable measures:

f

Protecting the cable by laying it appropriately, e.g.

in a protective sleeve.

f

Monitoring short circuits using an evaluation unit.

f

Using cable with individually screened cores. These

screens are to be connected to the machine or

plant earthing system. In this way cable short

circuits can be detected and the control system

shut-down immediately by the triggering of the

short circuit protection.

Setup

Check the enabling switch (enabling function at stage

2, and positively driven at stage 3) by performing

a functional check.
Depending on version: check the integrated func-

tions, such as stop button, key-operated rotary

switch, LEDs, etc.

Service and inspection

No servicing is required, but to ensure trouble-free

long-term operation, regular inspection of the electri-

cal and mechanical function is required.

In the event of functional faults or damage, the

enabling switch must be replaced. Repairs are

only to be made by the manufacturer!

Note: The year of manufacture can be seen in the

bottom, right corner of the rating plate.

Exclusion of liability under the following

circumstances

f

incorrect use

f

non-compliance with safety regulations

f

electrical connection not performed by authorized

personnel

f

non-implementation of functional checks.

EC declaration of conformity

The manufacturer named below herewith declares

that the product fulfills the provisions of the

directive(s) listed below and that the related stan-

dards have been applied.
EUCHNER GmbH + Co. KG

Kohlhammerstraße 16

70771 Leinfelden-Echterdingen, Germany
Directives and standards applied:
- Machinery directive 2006/42/EC

- EMC directive 2004/108/EC

- EN 60947-5-8:2006
Leinfelden, November 2010
Dipl.-Ing. Michael Euchner

Director
Duc Binh Nguyen

Authorized representative empowered to draw up

documentation
The signed EC declaration of conformity is included