I-Joist Installation

Use single I-joist for loads up to 2000 plf,

double I-joists for loads up to 4000 plf

(filler block not required)

Wall sheathing

as required.

Provide backer as required

for siding and/or wall

sheathing attachment

APA Rim Board may be used in lieu of

I-joists. Backer is not required when

APA Rim Board is used.

floor details

Wood

I Beam

blocking panel

Minimum 8d nails at 69 o.c.

F2

BLOCKING PANEL, EXTERIOR

Vertical load transfer = 2000 plf max.

Starter joist

Blocking where required

by local codes for lateral

load transfer and/or

optional blocking for

diaphragm nailing

Minimum

8d nails

at 6” o.c.

toe-nail

to plate,

typical

(3) 8d

nails at

corners

FiberStrong

rim board

One 2x4 min. with

1

8

9 gap at top,

fasten with 8d box nails from

each web into 2x_.

FiberStrong

rim board

8d nails

top and bottom flange

Check local building code for

appropriate detail in areas of

high lateral load.

Load bearing wall must stack over blocking and wall

or beam below.*

When two joists meet over wall,

provide 1

3

4

9 minimum bearing for

each joist and install blocking

panel to restrain both joists.

Blocking panels not required when

joists are continuous over wall and

no load bearing wall exists above.

Minimum 8d nails at 69 o.c.

*Non-stacking load bearing walls

require additional consideration.

F9

BLOCKING PANEL, INTERIOR

Vertical load transfer = 2000 plf max. along load bearing wall.

Headers can be single

or double I-joists.

Assemble double joist per

detail F11 (regular filler).

Backer Block (use if hanger load exceeds 250 lbs.)

Before installing backer to double joist, drive an additional (3) 10d nails into

web where backer will fit. Clinch when possible. Install backer tight to top

flange. Use (10) 10d nails, clinched when possible.

F12

FLOOR OPENING, TOP MOUNT HANGERS

FLOOR OPENING, TOP MOUNT HANGERS

Backer blocks required

both sides of web

(per hanger

manufacturer).

Hangers for 148

(max) Stringer

Nailing Requirement

United Steel

Minimum (12) 10d nails into

Products MSH 218

double joists or LVL header.

OR Simpson

Minimum (4) 10d x 1

1

2

9

Strong-Tie

®

THA 218 nails into stringer.

Toe-nail rim joist to top flange

of joist with 10d nail.

F5

F3

WOOD

I BEAM

RIM JOIST

Vertical load transfer = 2000 plf max.

* Block must be long enough to permit required nailing without splitting.

backer blocks

*

Joist Series

Joist Depth Material

Depth

GPI 20

9

1

2

9, 11

7

8

9,

23

32

9 6

1

4

9, 8

3

4

9,

149 10

3

4

9

GPI 40

9

1

2

9, 11

7

8

9,

7

8

9

6

1

4

9, 8

3

4

9,

149 10

3

4

9

GPI 65,

9

1

2

9, 11

7

8

9,

1

2

9 +

1

2

9

6

1

4

9, 8

3

4

9,

WI 40, WI 60

149, 169

10

3

4

9, 12

3

4

9

GPI 90, WI 80 11

7

8

9, 149, 169 1

1

2

9 net 8

3

4

9, 10

3

4

9,

12

3

4

9

SQUASH BLOCKS AT CONCENTRATED LOADS

1

16

9

gap

Solid block all posts

to bearing below

with equal number

of squash blocks.

For stair stringers longer than 148 or stringer reactions greater than 700 lbs.,

call Georgia-Pacific.

FIBERSTRONG

®

RIM CLOSURE

Vertical load transfer of 1

1

8

” rim board = 4850 plf

Double Wood

I Beam joist construction

per detail F11 (full depth filler); backer

block size and installation per

detail F12.

F8

Do not bevel cut

joist beyond inside

face of support.

Note: Wood

I Beam or

FiberStrong rim board

blocking, or x-bridging

required at bearing for

lateral support.

BEVEL CUT JOIST

Check local building

code for appropriate

detail in areas of high

lateral load.

F14

F19

F21

STAIR STRINGER TO

JOIST CONNECTION

Minimum

1

3

4

9 joist

bearing

at wall

Provide backer

for siding

attachment

unless nailable

sheathing is

used.

Minimum 8d nails at 69 o.c.

Wood

I Beam

rim joist

F10

SQUASH BLOCKS AT INTERIOR BEARING

Vertical load transfer = 2000 plf max along load bearing wall.

Check local

building code for

appropriate detail

in areas of high

lateral load.

Load bearing wall must stack over squash blocks and wall or beam below.

Non-stacking load bearing walls require additional consideration.

1

16

9

8d nail into

bottom flange

or plate

8d nail into

top flange

Squash block

(2x4 minimum) used only if

load bearing wall exists above

Bearing wall, GP Lam

®

LVL or

glulam beam

Attach joist with one

10d box or sinker nail on

each side of bearing.

Top mount

hangers*

GP Lam

®

LVL or Glulam Beam

Properly fastened bearing plate.

Plate must be flush with inside

face of steel beam. Plate

can overhang beam a

maximum of

1

4

9.

Steel Beam

Bearing stiffeners may be

required at hangers.

A

B

F15

JOIST TO BEAM CONNECTION

* Appropriate face mount hangers may be substituted. Properly fastened solid wood

blocking of the steel beam also required for face mount hangers on steel beam.

Top mount

hangers*

Installation Guide

Advertising