14

GeorGia-Pacific Wood Products

JaN 2014

caNadiaN iNstallatioN iNstructioNs

Pa

Ge

roof details (continued)

2G

Roof Opening, Face-Mounted Hangers

Backer block on both sides of
web (or backer block and filler
block, if multiple I-Joists), nail
with twelve-10d nails clinch
when possible.

Header may be I-Joist,
LVL, glulam, or lumber.

Bearing stiffeners required when
hanger does not support I-Joist top flange.

Filler blocking

(attach per

Fig. 1H)

Face-mount hanger

per hanger

manufacturer's

recommendation

2H

Birdsmouth Cut & Bevel Cut Bearing Stiffener

Bearing stiffeners required
each side of I-Joist.
Bevel cut bearing
stiffener to match
roof slope.

Four-8d nails (three each side)

clinched when possible.

Birdsmouth cut shall bear fully
on flange and not overhang the
inside face of plate.

" gap at top

One 10d box nail, face nail

at each side of bearing

(face nail where flange is

" to 1" thick)

2I

Birdsmouth Cut with Overhang (Permitted on low end of I-Joist only)

Bearing stiffener

required each side.

Attach joist to top
plate per Fig. 2H

Birdsmouth cut
at bearing

Note: Additional connection may be required for wind uplift. Outside
corner of blocking panel may be trimmed if it interferes with roof
sheathing. In such cases, position blocking panel on top plate to
minimize trimming and still allow required nailing into top plate.

Blocking panel

or x-bridging.

Bearing stiffener

(shown on blocking

panel side only)

Attach blocking

per Fig. 2A

1

/

8

" gap at top

2J

Blocking Panel at Beveled Plate

Attach I-Joist to beveled
plate per Fig. 2A

Blocking Panel
attach per Fig. 2A

Overhang

Beveled plate

Note: Additional connection

may be required for wind uplift.

2K

I-Joist with Bevel-Cut End

Do not bevel-cut joist

beyond inside face of wall

Attach per

Fig. 2A

Note: Blocking or
x-bridging required
at bearing for lateral
support, not shown
for clarity. Additional
connection may be
required for wind uplift.

2L

Outrigger

Notch 2x outrigger
around I-Joist

Do not notch I-Joist flange

Block between outriggers

End wall

Maximum overhang

same as rafter spacing

(not to exceed 2'-0")

Toe nail

blocking to end wall

for roof sheathing ≤ ".

Match nail type and spacing

with roof sheathing edge nailing.

Use minimum 8d nails.

Note: Additional connection
may be required for wind uplift.

All nails shown in the details below are assumed to be common nails unless otherwise noted. 10d box nails may be substituted for 8d common shown in details.

.

Individual components not shown to scale for clarity.

2'- 0"
max.

Permitted on low

end of I-Joist only

+

+

( ) designates nails from near face
(

+

) designates nails from far face

Legend

3

/

8

7

/

8

1

/

8