Automatic venting of a vacuum chamber, Max. turning the adjusting screw (6/2) clockwise – INFICON VSC150A absolute switch, passiv User Manual

Page 18

Advertising
background image

max. turning the adjusting screw (6/2) clockwise.

2.5.4 Automatic Venting of a Vacuum Chamber

to a Slight Overpressure

Assembly as in Fig. 9.

Loop the control circuit of the venting valve via the break
contact of the switching amplifier relay, terminals 12 and
13 (see Fig. 5). The switching pressure can be raised by
20 mbar max. above atmospheric pressure by turning
the adjusting screw (6/2) clockwise.

2.5.5 Differential Pressure Monitoring, Positive

and Negative Going

In an annealing plant with „holding vacuum“ pump down
and venting of the annealing pot and the vacuum fur-
nace must be regulated so that the differential pressures
in both directions will not exceed 10 mbar (Assembly as
shown in Fig. 10).

Starting from the basic adjustment set the two Vacuum
Switches by turning the adjusting screw (6/2) clockwise
so that at a pressure of 10 mbar in the reference cham-
ber against the pressure in the sensing chamber the
switch contact opens by flexing of the diaphragm. Con-
trol venting valves and pump valves each via the break

18

18

tina42e1 (2005-03) VSC150.ga

tina42e1 (2005-03) VSC150.ga

max. turning the adjusting screw (6/2) clockwise.

2.5.4 Automatic Venting of a Vacuum Chamber

to a Slight Overpressure

Assembly as in Fig. 9.

Loop the control circuit of the venting valve via the break
contact of the switching amplifier relay, terminals 12 and
13 (see Fig. 5). The switching pressure can be raised by
20 mbar max. above atmospheric pressure by turning
the adjusting screw (6/2) clockwise.

2.5.5 Differential Pressure Monitoring, Positive

and Negative Going

In an annealing plant with „holding vacuum“ pump down
and venting of the annealing pot and the vacuum fur-
nace must be regulated so that the differential pressures
in both directions will not exceed 10 mbar (Assembly as
shown in Fig. 10).

Starting from the basic adjustment set the two Vacuum
Switches by turning the adjusting screw (6/2) clockwise
so that at a pressure of 10 mbar in the reference cham-
ber against the pressure in the sensing chamber the
switch contact opens by flexing of the diaphragm. Con-
trol venting valves and pump valves each via the break

SV

SV

VSC 150

R

VSC 150

M

R

M

Oven

Crucible

Fig. 10

Differential pressure monitoring, positive and
negative going

VSC 150

M

R

SV

Fig. 9

Automatic venting between atmospheric pressure
and + 20 mbar

SV

SV

VSC 150

R

VSC 150

M

R

M

Oven

Crucible

Fig. 10

Differential pressure monitoring, positive and
negative going

VSC 150

M

R

SV

Fig. 9

Automatic venting between atmospheric pressure
and + 20 mbar

Advertising