I/o options and characteristics, I/o types and characteristics – B&B Electronics Zlinx 485 User Manual

Page 14

Advertising
background image

Hardware

Manual Documentation Number: Zlinx485m-1808

www.bb-elec.com

www.bb-europe.com

Figure 11. DIN Clip with Spring on a Zlinx 485 Module

I/O Options and Characteristics

I/O Options

The Zlinx 485 family of products features a variety of input and output options. Base and
expansion module options include:

• 2 analog inputs, 2 analog outputs, 2 digital inputs and 2 digital outputs (sourcing or

sinking driver)

• 4 digital inputs and 4 digital outputs (sourcing or sinking driver)
• 8 digital inputs
• 8 digital outputs (sourcing or sinking driver)

o

8 relay output model available

• 4 analog inputs

o

RTD Temperature input module available

• 4 analog outputs
• 2 analog inputs and 2 analog outputs
(Modules continue to be developed with additional features and options.)

Refer to Appendix E for a list of available models and options.

I/O Types and Characteristics

Digital Inputs

DI’s can detect the presence of contact closures, transistor switches or on/off DC voltage
signals (low or high logic levels). Voltages below 0.8 VDC are interpreted as a low state.
Voltages between 4.0 VDC and 48 VDC are interpreted as a high state.

DI’s are also programmable to be NPN or PNP