6 ups functionality, 7 "real time clock" functionality, 8 resetting the device (reset) – Lenze Controller 3200 C Operating Instructions User Manual

Page 22: Ups functionality, Real time clock" functionality, Resetting the device (reset), Product description

Advertising
background image

Product description

UPS functionality

3

22

Lenze ¯ BA_3231C ¯ 5.0

3.6

UPS functionality

In case of supply voltage failure, the UPS functionality (uninterrupted current supply) of
the device provides a backup function for saving the user data (retain variables, logbook
data) before the device will be switched off.

In order to minimise the power consumption and increase the safety during the buffer
times, circuitry parts that are not required can optionally be switched off during a supply
voltage failure (e.g. supply of the backplane bus, supply of the devices connected to the
USB ports).

Controller

3221 C / 3231 C

3241 C

UPS functionality via ...

Internal buffer capacitor

¯

External battery pack
(ACCU−PACK)

¯

External capacitor pack
(CAPS−PACK)

Storage medium for backup data

MRAM

SD/SDHC card

Buffer time sufficient for ...

60 kB of retain and logbook data

1 MB of retain and logbook data

,

Documentation for "ACCU−PACK"/"CAPS−PACK"

Here you can find detailed information on ...
¯ Battery pack (ACCU PACK);
¯ Capacitor pack (CAPS−PACK).

3.7

"Real Time Clock" functionality

The operating system contains the CMOS−RTC time via a maintenance−free chip.

The CMOS−RTC time is internally saved for a minimum period of 14 days. Then the time
must be set again manually via the »WebConfig« (parameter 91).

A battery is not

required.

3.8

Resetting the device (Reset)

To reset the device, press the reset button (

20).