Safety instructions – Lenze 3200 C User Manual

Page 12

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL/CSA

2

12

Lenze ¯ BA_3241C ¯ 4.0

2.3

Safety instructions for the installation according to UL/CSA

¸

Approval

Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142−M1987, (UL File Number
E236341)

Ratings

¯

Input 24 V DC, max. 1.7 A

¯

Max. Surrounding temperature:

45 °C, vertical (upright) mounting

50 °C, horizontal mounting

J

Warnings!

Field Wiring Markings
Wiring Terminal MSTB 2.5/3−STF−5.08:
¯ Use Copper Wire only.
¯ AWG 18 ... 12 (0.82 ... 3.3 mm

2

)

¯ Torque 5 ... 7 lb−in (0.5 ... 0.6 Nm)
Device
¯ These devices are open type programmable controllers, provided with

housing for use in pollution degree 2 and controlled environment only.

¯ For use in max. surrounding temperature:

– 45 °C, vertical (upright) mounting
– 50 °C, horizontal mounting

Optional filed bus module
¯ Use only together with appropriate cable connectors, provided with

screws for securement and secure connector to avoid loosening.

Advertising