Electrical installation

Connecting voltage supply (24 V)
Connection plan

6

30

Lenze ¯ BA_3241C ¯ 4.0

6.3

Connecting voltage supply (24 V)

(

Stop!

No device protection against excessive input voltage
The voltage input is not fused internally.
Possible consequences:
¯ The device can be destroyed when the input voltage is too high.
Protective measures:
¯ Observe the max. permissible input voltage.
¯ Professionally fuse the device on the input side against voltage

fluctuations and voltage peaks.

)

Note!

The IPC boots up as soon as the supply voltage is applied.
After the operating system has been shut down, the IPC switches off
automatically. For restarting, the supply voltage has to be disconnected
for a short time.

6.3.1

Connection plan

L1

N

PE

L1 N

+

0V

+24

+

~

=

0 VPE +24 V

+

0

1

F

2

CPC2xx−006

Fig. 6−1

Connection plan for voltage supply (24 V)

Pos.

Description

A

IPC

B

Power supply unit

C

PE conductor connection on the supply side via DIN rail

6.3.2

Mains connection (24 V)

Figure

Connection

Connection type

Cable type

0V

U

X1:
DC voltage supply (24 V)

3−pin Combicon socket

Cable with Combicon plug

(conductor cross−section

max. 2.5 mm

2

)

IPC001