Electrical installation − EMS version

Control terminals
Interfaces RS485 PLC

7

l

134

EDS84DPS424 EN 5.0

7.6.5

Interfaces RS485 PLC

These connections are available with device versions:

ƒ

E84DDxxxxxxxCxBxxx

ƒ

E84DExxxxxxxCxBxxx

ƒ

E84DFxxxxxxxCxBxxx

ƒ

E84DLxxxxxxxCxBxxx

ƒ

E84DPxxxxxxxCxBxxx

X81/X82 − RS485 PLC

Pin

Signal

Description

Data

84DPSO05_8

M12 type, 8−pole sockets, A−coded

1

TxD+

RS485A

In accordance with ANSI/TIA/EIA−485−A−98

2

TxD−

RS485B

3

RxD+

RS485A’

4

RxD−

RS485B’

5

n. c.

Not assigned

6

n. c.

7

GND−EXT

Reference potential

In accordance with IEC 61131−2, type 1

8

+24V

24 V supply