6electrical installation, Ewz0046 – Lenze EMF2180IB EthernetCAN User Manual
Page 48

6
Electrical installation
Connection of system bus (CAN)
EDKMF2180 DE/EN/FR/ES/IT 3.0
48
H1_E_INST-SteckerFederkraftAnschluss FKCT
Between CAN_LOW and CAN-HIGH the CAN bus has to be terminated by resistors (120
Ω
).
The Sub-D plug with an integrated terminating resistor (order no. EWZ0046, not included
in the scope of supply) complies with the recommendation DS 102-1 of CiA.
L
EWZ0046
OFF
ON
OFF
ON
ON
OFF
р
р
р
р
OUT
IN
IN
IN
On
Off
On
120
120
120
L
EWZ0046
L
EWZ0046
L
EWZ0046
2181FEW004
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898-2:
CAN cable in accordance with ISO 11898-2
Cable type
Paired with shielding
Impedance
120
Ω
(95 ... 140
Ω
)
Cable resistance/cross-section
Cable length
≤
300 m
≤
70 m
Ω
/m / 0.25 … 0.34 mm
2
(AWG22)
Cable length 301 … 1000 m
≤
40 m
Ω
/m / 0.5 mm
2
(AWG20)
Signal propagation delay
≤
5 ns/m
Observe the information on the bus cable length(49)!