6electrical installation, Ewz0046 – Lenze EMF2180IB EthernetCAN User Manual

Page 48

Advertising
background image

6

Electrical installation

Connection of system bus (CAN)

EDKMF2180 DE/EN/FR/ES/IT 3.0

48

H1_E_INST-SteckerFederkraftAnschluss FKCT

Between CAN_LOW and CAN-HIGH the CAN bus has to be terminated by resistors (120

).

The Sub-D plug with an integrated terminating resistor (order no. EWZ0046, not included
in the scope of supply) complies with the recommendation DS 102-1 of CiA.

L

EWZ0046

OFF

ON

OFF

ON

ON

OFF

р

р

р

р

OUT

IN

IN

IN

On

Off

On

120

120

120

L

EWZ0046

L

EWZ0046

L

EWZ0046

2181FEW004

Specification of the transmission cable

We recommend the use of CAN cables in accordance with ISO 11898-2:

CAN cable in accordance with ISO 11898-2

Cable type

Paired with shielding

Impedance

120

(95 ... 140

)

Cable resistance/cross-section

Cable length

300 m

70 m

/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

40 m

/m / 0.5 mm

2

(AWG20)

Signal propagation delay

5 ns/m

Observe the information on the bus cable length(49)!