Technical data
General data and operating conditions
EDKRBP082R DE/EN/FR/ES/IT 7.0
43
l
H1_Daten−AbmERBP_BL
Mounting conditions
Mounting location
l
In the control cabinet
l
The mounting location must comply with the
device features mentioned in the chapter "General
data".
l
Flammable materials or substances may not be
placed in the vicinity of the brake resistor.
l
The heat generated by the brake resistor must be
dissipated freely.
Mounting position
Standard
Vertically suspended with connections at the bottom.
Variant
Horizontally standing with fixing bracket at the
bottom. The permanent power P
d
is to be reduced by
30 %!