Commissioning – Lenze E94AYCIB User Manual
Page 49
Advertising

Commissioning
DIP switch settings
EDK94AYCIB DE/EN/FR/ES/IT 1.0
49
l
H1inbet−ueb−rate einstellen
Setting the number of parameter data words (PCP)
ƒ You can use switches 5 and 6 or the code C13892 / C14892 to set the number of
parameter data words.
ƒ 0, 1, 2 or 4 parameter data words can be used.
ƒ The current setting is shown in C13860/1 / C14860/1.
)
Note!
The total number of data words (PD + PCP) must be between 1 and 10.
Impermissible settings are signalled by the "BE" LED (flashes
^ 51
The communication module then works internally with the following values:
ƒ
PD = 2 (words)
ƒ
PCP = 1 (word)
DIP switch
Number of PCP
Switch
Max. number of
PD
ID code
[hex]
5
6
12345678
ON
OFF
0
OFF
OFF
10
0x03
1
OFF
ON
9
0xE3
2
ON
OFF
8
0xE0
4
ON
ON
6
0xE1