2 electrical installation, 2electrical installation – Lenze E94AYCEC User Manual

Page 18

Advertising
background image

2

Electrical installation

EDK94AYCEC DE/EN/FR/ES/IT 1.0

18

l

H1_E_INST−−−−(DUMMYSEITEVOR)−−−

2

Electrical installation

External voltage supply

Supply the communication module via the connection X210 by means of a separate supply
voltage.

Designation

Explanation

+

External voltage supply
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 140 mA

Reference potential for external voltage supply

For greater distances between the control cabinets, use a power supply unit in each control
cabinet.

Screw terminal data

Plug connector with screw connection

Possible connections

rigid: 1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve
1.5 mm

2

(AWG 16)

Tightening torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)

Bare end

6 mm

Advertising