Electrical installation

External voltage supply

6

EDK94AYCER DE/EN/FR/ES/IT 6.0

43

l

H2_ext_SpannVersorg−Steckerleiste_Federkraft

External voltage supply

)

Note!

Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.

The external voltage supply of the communication module is necessary if PROFINET
communication is to continue in the event that the power supply to the standard device is
cut off.

Supply the communication module via the 2−pole plug connector (X240) with a separate
supply voltage.

Designation

Description

+

External voltage supply
U = 24 V DC (20.4 V ... 28.8 V)
I = 130 mA

Reference potential for external voltage supply

Terminal data

Field

Values

Electrical connection

2−pin plug connector with spring connection

Possible connections

rigid:

1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve
1.5 mm

2

(AWG 16)

Stripping length

9 mm