Electrical installation

Assignment of the terminals

EDK10201EZ3 DE/EN/FR 5.1

16

l

H1_E_INST−Belegung_10201_en

Terminal

Signal type

Function

Technical data

Remarks

X1/

^

24

GND, reference potential

X2/+O24

DC supply voltage

18 VDC ... 30 VDC

Connected via
emergency off at the
Drive PLC

X2/VBr

DC supply voltage for
X3/O9, X3/O10

18 VDC ... 30 VDC

Always conduct via
emergency off

X3/O5

Digital
outputs

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max. 1 A

X3/O6

X3/O7

X3/O8

X3/O9

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max. 2 A

Suitable for brake
control

X3/O10

X4/I9

Digital
inputs

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V

X4/I10

X4/I11

X4/I12

X4/I13

X4/I14

(

Stop!

ƒ

Ensure a sufficient dimensioning of the DC voltage supply, if the loads are
connected to the digital outputs.

ƒ

The extension board must exclusively be supplied separately.The internal
supply via the Drive PLC is not permissible.