Electrical installation

Wiring according to EMC (installation of a CE−typical drive system)

4

l

51

EDKCSCK002 DE/EN/FR 1.1

Shielding

ƒ

Connect the motor cable shield to the axis module

–

with the shield mounting kit ECSZS000X0B001.

–

to the mounting plate below the axis module with a large surface.

–

Recommendation: For the shield connection, use earthing clamps on bare
metal mounting surfaces.

ƒ

If contactors, motor−protecting switches or terminals are located in the
motor cable:

–

Connect the shields of the connected cables and connect the shields to the
mounting plate, too, with a surface as large as possible.

ƒ

Connect the shield in the motor terminal box or on the motor housing to PE:

–

Metal glands at the motor terminal box ensure a large−surface connection
of the shield and the motor housing.

ƒ

Shield the control cables:

–

Connect both shield ends of the digital control cables.

–

Connect one shield end of the analogue control cables.

–

Always connect the shields to the shield connection at the axis module
over the shortest possible distance.

ƒ

Using the axis modules in residential areas:

–

Additionally dampen the shield in order to limit the interfering
radiation:

≥ 10 dB. This can be realised by using standard, closed, metallic,

and earthed control cabinets or boxes.

Earthing

ƒ

Earth all metallically conductive components (e. g. power supply module,
capacitor module, axis module, RFI filter, motor filter, mains choke) using
suitable cables connected to a central point (PE bar).

ƒ

Maintain the minimum cross−sections prescribed in the safety regulations:

–

For the EMC, not the cable cross−section is important, but the cable surface
and the contact with a surface as large as possible.