Troubleshooting and fault elimination

System error messages
General error messages

4

l

38

EDKVF93−04 EN 2.0

Remedy

Cause

Error

Error number

x = 0: TRIP
x = 1: Message
x = 2: Warning

Display

OH

x050

Heatsink
temperature is
higher than the
value set in the
controller

Ambient temperature T

u

> 40 °C or 50 °C

l

Allow controller to cool and ensure
better ventilation

l

Check ambient temperature in the
control cabinet

Heatsink very dirty

Clean heatsink

Wrong mounting position

Change mounting position

OH3

x053

Motor temperature
is higher than the
value set in the
controller

Motor too hot because of excessive
current or frequent and too long
acceleration

Check drive dimensioning

No KTY is connected to X8

Connect KTY or switch off monitoring
(C0583 = 3)

OH4

x054

Heatsink
temperature is
higher than the
value set in C0122

Ambient temperature T

u

> 40 °C or

50 °C.

l

Allow controller to cool and ensure
better ventilation

l

Check ambient temperature in the
control cabinet

Heatsink very dirty

Clean heatsink

Wrong mounting position

Change mounting position

The value entered in C0122 is too low

Enter higher value

OH7

x057

Motor temperature
is higher than the
value set in C0121

Motor too hot because of excessive
current or frequent and too long
acceleration

Check drive dimensioning

No KTY is connected to X8

Connect KTY or switch off monitoring
(C0584 = 3)

The value entered in C0121 is too low

Enter higher value

OH8

x058

PTC at terminals
T1, T2 indicates
motor overheating

Motor too hot because of excessive
current or frequent and too long
acceleration

Check drive dimensioning

Terminals T1, T2 are not assigned

Connect PTC or thermal contact or
switch off monitoring (C0585=3)

OU

x020

Overvoltage in the
DC bus

Only for variants V210, V240, V270,
V300:

l

Wrong values in C0173

l

Wrong values in C0174

l

Set correct values in C0173

l

Set correct values in C0174

PEr

x074

Program fault

An error has been detected in the
program flow. The parameter set 1 is
loaded automatically. Parameter data
which has been changed and not has
been saved, will get lost.

Contact Lenze

PI

x079

Initialisation error

l

A fault was detected during transfer
of parameter sets between the
controllers

l

Parameter set does not match the
controller

Correct parameter set

PR0

x075

Parameter set error Error while loading a parameter set. The

parameters saved do not match the
software version of the controller.
CAUTION! The Lenze setting is loaded
automatically.

l

Correct parameter set

l

Save all parameter sets with C0003
and reset the fault message by mains
switching

PR1
PR2
PR3
PR4

x072
x073
x077
x078

Parameter set error

l

Fault while loading a parameter set

l

The transmission of parameter sets
with keypad XT has been interrupted
(e.g. by an early disconnection of the
keypad XT)

CAUTION! The Lenze setting is loaded
automatically.

Set the required parameters and save
them with C0003

Sd3

x083

Encoder error at X9 Cable interrupted

Check cable for wire breakage