EDKLN3LR−4 DE/EN/FR/ES/IT 3.0

5

l

KFZ_Zeichen_EN−TD_BemDaten_sTypensch

Technical data

Enclosure

EN 60529

IP 00

NEMA 250

Protection against accidental
contact according to type 1

Insulation resistance

EN 61800−5−1

Overvoltage category III
> 2000 m: Overvoltage category II

Class of insulation

H (permissible up to 180 °C)
In continuous operation with rated data, high surface
temperatures are reached!

Temperature

Storage

−25 ... +60 °C

Transport

−25 ... +70 °C

Operation

−10 ... +55 °C (Temperature in the control cabinet)
Current derating from +40 ... +55 °C: 2.5 %/°C

Pollution

EN 61800−5−1

Pollution degree 2

Vibration resistance

EN 50178; IEC
61800−5−1;
Germanischer
Lloyd, general
conditions

Acceleration−resistant up to 1 g

Mounting location,
mounting position

In the control cabinet, recommended: Suspended with horizontal
alignment,

^ 13

(with greater masses, standing is also an option)

Rated data,
conformity/approval

See nameplate
For power loss see table,

^ 12