Application range – Lenze E82ZM222 Motor filter User Manual

Page 20

Advertising
background image

EDK82ZM222 DE/EN/FR 2.1

20

l

DUMMY_NUM_Reset−TIP_download_EN

Application range

Motor filters are applied to reduce the motor cable load and to decrease capacitive
discharge currents to PE in long motor cables.

A motor filter is required:
ƒ in very long motor cables (regardless of the compliance with EMC limit values)

– 50 m when low−capacitance shielded (max. 100 m)
– 100 m when unshielded (max. 200 m)
Motor cables must comply with EMC limit values only with regard to conducted
interference emission.

ƒ in combination with LD RFI filters (0.25 ... 11 kW)

– for reducing the conducted noise emission when long motor cablesare used
– for compliance with EMC limit class C1 or C2

ƒ When operating motors whose insulation systems are not suitable for inverter

operation. Lenze motors have insulations with greater thermal reserves.

Please note:
ƒ Operation is only permissible if a V/f or V/f

2

characteristic control and a switching

frequency of 2 ... 8 kHz is applied.
– The filter will overheat if it is operated at another switching frequency.

ƒ The frequency inverter is loaded with an additional 12 per cent, approximately, of the

rated current of the motor filter.

ƒ The voltage drop at the motor filter averages 2−3 per cent of the max. output voltage

of the frequency inverter if the rated current of the motor filter and a frequency of 50
Hz is applied.

Assignment of filters to standard devices

Mains

Controller type

P

r

[kW]

Type of filter

1 ~

230 V

E82xV251K2

0.25

E82ZM222232B

E82xV371K2

0.37

E82xV551K2

0.55

E82xV751K2

0.75

E82xV152K2

1.5

E82xV222K2

2.2

3 ~

230 V

E82xV551K2

0.55

E82xV751K2

0.75

E82xV152K2

1.5

E82xV222K2

2.2