Lenze ERBGxxxxxxxx User Manual

Page 52

Advertising
background image

Electrical installation

Mounting steps

6

l

52

EDKRBG018R DE/EN/FR/ES/IT 8.0

How to connect the brake resistor:
1. Disconnect the basic device from the mains and check that no voltage is

applied to the power terminals.

2. Remove the terminal cover.
3. Connect the brake resistor cable:

–

Use a twisted cable for cables up to 0.5 m (connection plan variant 1).

–

Use a shielded cable for cables up to 5 m (connection plan variant 2).

–

Pass the cable through the cable gland

0.

–

Connect the cores to connections RB1, RB2 and PE of the brake resistor
observing the tightening torque. PE connection to EN 61800−5−1.

–

Tighten the cable gland

0.

For shielded cables: Securely connect the shield to the cable gland with
a surface as large as possible.

–

Connect cores and shield to the basic device observing the
documentation for the basic device.

4. Connect the thermal contact cables:

–

Use a twisted cable.

–

Pass the cable through the cable gland

1.

–

Connect the cores to connections T1 and T2 of the brake resistor
observing the tightening torque.

–

Tighten the cable gland

1.

–

When integrating the thermal contact into the system monitoring
ensure that the mains supply will be switched off when the brake
resistor is overheated.

5. Mount the terminal cover.

)

Note!

If the brake resistor is switched on for the first time or has not been
used for a longer period of time, a smell may develop together with
a low smoke emission. This is harmless.

Advertising