19.1.158.9 Action type "Variable branching"

For variable branching (jumps), two actions of "variable branching" type are available.

• Branching to one of 20 possible steps is carried out depending on the wBranch1 input signal or

wBranch2 input signal at the time of processing.

• wBranch1 input signal defines branching for action 1.
• wBranch2 input signal defines branching for action 2.

• Example: If the wBranch2 input signal has the value "15" at the time of processing of the action

no. 2, it is branched to the step entered in the parameter "Var. branching n: Jump destination

15" for action no. 2 (

C01432/2

).

Action call (entry in the sequence table)

with action number xxx = 001 ... 002

Parameter
The available actions 1 ... 2 are represented via the subcodes 1 ... 2.

Parameter

Possible settings

Info

C01418/1...2

...

C01437/1...2

Var. branch n: Jump destination 1 ...

20

• Branch destinations 1 ... 20 for

input values 1 ... 20 of

wBranch1...2.

0 Branching deactivated

(The following step in the sequence

table is processed.)

1...100 Step 1 ... 100

1

n

2

4 x x x