5

Motor control (MCTRL)

5.10

Parameterisable additional functions

278

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• In

C000937/1

, the actually used maximally effective field-producing motor current is displayed.

• With switched-on and active field weakening: 0.00 A ... -x.xx A
• With sensorless control for synchronous motors (SLPSM), the injected current is displayed in

open-loop controlled operation: 0.00 A ... +x.xx A

• If neither field weakening nor open-loop controlled operation are active,e "0.00 A" is

displayed.

Note!

If a Lenze motor is used:
The controller is automatically parameterised so that field weakening operates

optimally and the maximally permissible speed is monitored.

Stop!

If an OEM motor is used:
If pulse inhibit is set in the controller, the DC bus is loaded with the voltage that

corresponds to the current speed of the machine.
Since with switched-on field weakening higher speeds can be achieved at a

correspondingly higher rotor voltage of the motor, the DC bus can be loaded to a voltage

higher than the set DC-bus voltage in case of pulse inhibit and a currently high motor

speed and even exceed the maximally permissible voltage of 800 V!
For device protection, either use a brake chopper or parameterise the motor speed

monitoring via

C00965

in such a way that only a maximum speed is possible which

would be also reachable without field weakening with a DC-bus voltage of = 800 V.

Motor speed monitoring

( 304)