Model TE-703/704

Technical Information

TI.703/704-03

PIPE TEMPERATURE SENSORS

Page 3 of 4

RoHS

CHECKOUT

Allow the sensor to stabilize in (or against) the pipe for a minimum of five

minutes before taking a resistance measurement.

1. Disconnect the sensor lead wires from the controller.
2. Connect an ohmmeter across the lead wires.
3. Ensure that nominal resistance measurements are in accordance

with the resistance/temperature curves. (Refer to Tables 1 & 2.

For complete Resistance vs. Temperature tables, please refer to

TI.700-11 - Temperature Sensor section.)
4. Reconnect sensor lead wires to the controller.
5. Check operation of the complete control system.

Figure 3 - Installing the TE-704-B, TE-704-C, or TE-704-D Sensor

MAINTENANCE

Regular maintenance of the total system is recommended to

assure sustained optimum performance.

FIELD REPAIR

None. Replace with a functional unit.

DIMENSIONAL DATA

TE-703/704 Pipe Temperature Sensors dimensions shown in inches and

millimeters (mm).

Figure 4

TE-703-A

Figure 6

TE-703-C & TE-703-D

Figure 5

TE-703-B

Figure 7

TE-704-B

1/4" (6.3 mm)

9/16" Hex

1/4" (6.3 mm)

1/4" (6.3 mm)

2.00"

(50 mm)

1.20"

(30 mm)

1.20"

(30 mm)

2.50"

(62 mm)

2.50"

(62 mm)

2.00"

(50 mm)

4.00"

(100 mm)

5.00"

(124 mm)

2.50"

(62 mm)

2.00"

(50 mm)

3.50"

(90 mm)

4.30"

(110 mm)

Sensing

element

Pipe

clamps

Pipe

Advertising
This manual is related to the following products: