Model TE-701/702

Technical Information

TI.701/702-03

DUCT TEMPERATURE SENSORS

Page 2 of 4

RoHS

TE-701-A or B: Refer to Figure 4 for mounting dimensions.

1. Drill a 3/8-inch (9 mm) hole into the duct or plenum where the sensor will

be installed.

2. Insert the sensor probe into the duct or plenum until the flange rests

against the duct or plenum wall.

3. Use the flange as a template to mark and drill holes for two #8 self-tapping

sheet metal screws (not provided).

4. Fasten the sensor to the duct or plenum wall with the sheet metal screws.
5. Make the wiring connections. Refer to Figure 1.

Mounting

Location: Install the sensor in a location where it will sample the average air

temperature in a duct. Avoid areas where the air is stratified because these areas

can cause sensing errors.

TE-701-C or D: Refer to Figure 5 for mounting dimensions.

1. Drill a 3/8-inch (9 mm) hole into the duct or plenum where the

sensor will be installed.

2. Remove the mounting nut from the bulkhead fitting.
3. Insert the sensor probe into the duct or plenum until the bulkhead

fitting rests against the duct or plenum wall.

4. Guide the nut along the probe and tighten against the duct or

plenum.

5. Make the wiring connections. Refer to Figure 2.

TE-702-A, B, or C: Refer to Figures 6 & 7 for mounting dimensions.

1. Drill a 3/8-inch (9 mm) hole into the duct or plenum where the

sensor will be installed.

2. Insert the sensor probe into the duct or plenum until the mounting

bracket rests against the duct or plenum wall.

3. Use the mounting bracket as a template to mark and drill holes for

two #8 self-tapping sheet metal screws (not provided).

4. Fasten the sensor to the duct or plenum wall with the sheet metal

screws.

5. Loosen the cover screws and rotate the cover out of the way.
6. Make the wiring connections. Rotate and screw the cover back

into place. Refer to Figure 3.

Figure 1 - Installing the TE-701-A or TE-701-B Sensor

Figure 2 - Installing the TE-701-C or TE-701-D Sensor

Figure 3 - Installing the TE-702-A, TE-702-B, or TE-702-C Sensor

Inspection

Requirements

INSTALLATION

Inspect the package for damage. If damaged, notify the

appropriate carrier immediately. If undamaged, open the

package and inspect the device for obvious damage.

Return damaged products.

Do not use on oxygen service, in an explosive/hazardous

environment, or with flammable/combustible media.

Disconnect power supply before installation to prevent electrical

shock and equipment damage.

Make all connections in accordance with the job wiring diagram

and in accordance with national and local electrical codes. Use

copper conductors only.

Use electrostatic discharge precautions (e.g., use of wrist

straps) during installation and wiring to prevent equipment

damage.

Avoid locations where severe shock or vibration, excessive

moisture or corrosive fumes are present. NEMA-4 housings are

intended for outdoor use primarily to provide a degree of

protection against wind-blown dust, rain, and hose-directed

water.

Do not exceed ratings of the device.

Tools (not provided)

- Digital Volt-ohm Meter (DVM)

- Appropriate screwdriver for mounting screws

- Appropriate drill and drill bit for mounting screws

Appropriate accessories

Two #8 self-tapping mounting screws (not provided)

Training: Installer must be a qualified, experienced technician.

Warning:

Caution:

Probe

Two #8 self-tapping

screws (not included)

System duct

or plenum

System duct

or plenum

Probe

Bulkhead

fitting

System duct

or plenum

1/2

"

knockout

Two #8 self-tapping

screws (not included)

Probe