EP-311/313 ELECTROPNEUMATIC TRANSDUCER INSTALLATION INSTRUCTIONS

Figure 3 - Terminal Locations on EP-311/313

Installation Adjustments:

The EP-311/313 is supplied from the factory

set for 4-20 mA. To change the input configuration, adjust the Dip switch

settings as illustrated in

Figure 4 (below).

CHECKOUT

1. Verify that the unit is mounted in the current position.

2. Verify appropriate supply voltage.

3. Verify appropriate input configuration.

TRANSDUCER OPERATION

This is a rough functional check only.

1. Adjust the input signal to obtain maximum output pressure for

appropriate range.

2. Output should be 15 or 20 PSIG.

3. Adjust the input signal to obtain minimum output pressure.

4. Output should be 0 or 3 PSIG.

CALIBRATION

All units are factory calibrated to meet or exceed published specifications.

If field adjustment is necessary, follow the instructions below.

1. Connect air to main port.

2. Connect branch port to an accurate gauge with a minimum 6 to 10 ft.

(1.8 to 3.0m) of tubing.

CAUTION: NEVER connect 120 VAC to these transducers!

3. Connect terminals + and - to the appropriate power source for this unit.

The EP-311/313 can accept either 24 VAC or 24 VDC supply voltage.

The maximum supply voltage should not exceed 30 VAC/VDC.

4. Apply low input signal to terminals - and I (0 VDC or 4 mA).

5. Adjust Z to obtain desired output low pressure.

6. Apply high input signal to terminals - and I (5/10 VDC or 20 mA).

7. Adjust S to obtain desired output high pressure.

8. Repeat Steps 4-7 until the unit is completely calibrated.

MAINTENANCE / FIELD REPAIR

Regular maintenance of the total system is recommended to assure sustained

optimum performance. No field repair is possible. Replace suspect devices

with a functional unit.

WARRANTY

See Data Sheet for additional information.

Figure 5 - EP-311/313 Electropneumatic Transducer Dimensions

shown in inches and millimeters (mm)

Figure 4

Dip Switch Settings on

EP-311/313

For Technical / Application Assistance call your nearest office

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

EUROPE

4200 Waterside Centre

Solihull Parkway

Birmingham • West Midlands

B37 7YN • United Kingdom

01384-271113 • Fax 01384-271114

AUSTRALIA

4 Armiger Court, Unit 2

Adelaide • S.A.

5088 • Australia

08-8395-4333 • Fax 08-8395-4433

CANADA

675 Cochrane Drive

East Tower • 6th Floor

Toronto • Ontario

L3R 0B8 • Canada

905-474-9215 • Fax 905-474-0876

ASIA

1 Fullerton Road #02-01

One Fullerton

Singapore • 049213

65-31581826 • Fax 65-31581826

MAMAC Systems, Inc., reserves the right to change any specifications

without notice to improve performance, reliability, or function of our products.

Advertising
This manual is related to the following products: