SECTION 1 - Wiring

Terminate the IP Sensor Appliance as shown in fig. 3.

Use a UL rated 24VAC class-2 transformer or a UL rated 24VDC power supply with

transformer isolation.

WARNING:

Maximum supply voltage MUST NOT EXCEED 35VAC/35VDC.

CAUTION:

The appliance and all sensors connected must be wired with all neutral/common

connections with the same polarity. All sensors and the appliance neutral/common must

terminate at the transformer/power supply neutral/common.

Digital inputs are terminated as shown in fig. 4.

MAMAC SYSTEMS

Figure 4

Digital

Input #2

Digital

Input #1

WARNING: Digital Input
must not exceed 10.0 VDC.

Signal

Common

Supply

Signal

Common

Supply

Signal

Common

Supply

Sensor “n”

Sensor 2

Neutral/Common
24 VDC/VAC

Sensor 1

MAMAC SYSTEMS

Note: Use 18 gauge conductor
for

ground.

Note:

Always disconnect

power

from

unit

before

wiring a sensor.

Figure 3

24 VAC/VDC

TRANSFORMER/POWER SUPPLY