Dca-150ssvu — output terminal panel connections – Multiquip DCA150SSVU User Manual

Page 34

Advertising
background image

PAGE 34 — DCA-150SSVU— OPERATION AND PARTS MANUAL (STD) — REV. #1 (06/03/03)

Figure 21. Voltage Selector Switch 240/139V

Three-Phase Position

DCA-150SSVU — OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are de-
pendent on the position of the

Voltage Selector Switch and

the adjustment of the

Voltage Regulator Control Knob.

Remember the voltage selector switch determines the

range

of the output voltage. The voltage regulator (VR) allows the
user to increase or decrease the selected voltage.

3Ø 240/139 UVWO Terminal Output Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in Figure 21.

Figure 22. UVWO Terminal Lugs

240/139V Three Phase Connections

2. Connect the load wires to the UVWO terminals as shown

in Figure 22.

3. Turn the voltage regulator knob (Figure 23) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

3Ø 208V/1Ø120V UVWO Terminal Output Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in Figure 24.

Figure 23. Voltage Regulator Knob (139V/240V)

Use this position for
3Ø-208 or 1Ø120V.

2. Connect the load wires to the UVWO terminals as shown

in Figure 25.

3. Turn the voltage regulator knob (Figure 26) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

Figure 26. Voltage Regulator Knob (208V)

NOTE

To achieve a 3Ø 208V
output the voltage selector
switch must be in the 3Ø-
240/139 position and the
voltage regulator must be
adjusted to 208V.

Figure 25. UVWO Terminal Lugs

3Ø-208V/120V Connections

Figure 24. Voltage Selector
Switch 3Ø-208V/1Ø-120V
Three-Phase Position

Advertising