Dca-150ssvu — output terminal panel connections – Multiquip DCA150SSVU User Manual

Page 35

Advertising
background image

DCA-150SSVU— OPERATION AND PARTS MANUAL (STD)— REV. #1 (06/03/03) — PAGE 35

Figure 27. Voltage Selector Switch 480/277V

Three-Phase Position

3Ø 480/277 UVWO Terminal Output Voltages

1. Place the voltage selector switch in the 3Ø 480/277

position as shown in Figure 27.

Figure 28. UVWO Terminal Lugs

240/139V Three Phase Connections

2. Connect the load wires to the UVWO terminals as shown

in Figure 28.

3. Turn the voltage regulator knob (Figure 29) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

1Ø 240V/120V UVWO Terminal Output Voltages

1. Place the voltage selector switch in the 1Ø 240/120

position as shown in Figure 30.

Figure 29. Voltage Regulator Knob (139V/240V)

2. Connect the load wires to the UVWO terminals as shown

in Figure 31.

3. Turn the voltage regulator knob (Figure 32) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

Figure 32. Voltage Regulator Knob (1Ø-240/120V)

Figure 31. UVWO Terminal Lugs

1Ø-240V/120V Connections

DCA-150SSVU — OUTPUT TERMINAL PANEL CONNECTIONS

Figure 30. Voltage Selector Switch 240/120V

Single-Phase Position

Advertising