Caution, Caution caution, Dca-150ssvu — generator shut-down procedure – Multiquip DCA150SSVU User Manual

Page 45

Advertising
background image

DCA-150SSVU— OPERATION AND PARTS MANUAL (STD)— REV. #1 (06/03/03) — PAGE 45

Shutdown Procedure - Engine Controller

To shutdown the generator use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 44 to the "OFF position".

2. Place the engine speed switch in the “LOW” position

(Figure 64).

Figure 64. Engine Speed Switch (Low)

3. Let the engine cool by running it for 3-5 minutes with no

load applied.

4. Place the Auto-Off/Reset-Manual switch (Figure 65) to

the

OFF/Reset position.

Figure 65. Off/Manual Auto Switch (Off)

5. Verify that the

all status LED on the MPEC display

(Figure 52) are "OFF" (not lit).

6. Remove all loads from the generator.

NEVER stop the engine suddenly except
in an emergency. DO NOT use the

emergency stop switch a as method of
shutting down the generator. This switch is
ONLY to be used in the event of an

emergency.

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION:

Emergency Shutdown Procedure - Engine Controller

1.

To shut-down the engine in the event of an
emergency, switch the

MAIN, GFCI and LOAD

(Figure 44) circuit breakers to “OFF” position.

2.

Place the Auto-Off/Reset-Manual switch (Figure 65)
to the “OFF/Reset“ position.

DCA-150SSVU — GENERATOR SHUT-DOWN PROCEDURE